| Application scope |
| It can protect the electric line equipment from overload and short circuit. |
| |
Technical parameter
Electric parameter:
Up to electrical standard: EN60898 GB10963 IEC898
Rated voltage (Ue): 230/400V. 50/60HZ
Rated breaking capacity: 10KA IEC898(0.5 -63A )
15KA IEC947-2(0.5 -63A )
DC short circuit breaking capacity: Max 48V(L7-10KA)single-pole
Max 250V(L7-DC,6KA)single-pole
Characteristic curve B,C,D
Max connectable fuse: 100AgL(>10KA)
Working ambient temperature: -5~+ 4 0 ?
Enclosed protective class:IP40 (under mounting)
Service life:Electric no less than 8000 times make-break operation
Mechanical parameter:
Exposed face length: 45mm
Casing height: 80mm
Casing width: 17.5mm /pole(single-pole) 26.3mm :1P+N(1.5 modules)
Installation mode: adopting IEC standard guide rail 35mm
Terminal form: The double function terminal can connect with busbar and conductor.
Connecting capacity of terminal: conductor1 -25mm 2 (excepted 1P+N)
1 -25 mm 2 /1 -210 mm 2 (N)(1P+N)
Busbar thickness:0.8 -2mm |
| |
|
|
|
 |
|