Application
Series G5SM1 earth leakage breakers apply to AC circuitof frequency of 50HZ, rated voltage up to 415V, rate current up to 80A . It is mainly used as an indirect contact protection for human. It also can be used to prevent against the fire danger caused by earth falt current owing to equipment insulation damage. When the proective measures of the electric shock are out of work, the RCCB whose rated residual operating current less than 30mA can serve as the suppplementary protection for in direct contact, but it can't be used as the sole direct contact protection.
Product features
Series G5SM1 Leakage Breakers are the protector for pure electromagnetic residual current operation.
The operation function is unrelated to circuit voltage, but operation is reliable.
It can be reliably operated on the loss of phase or neutral
The capacity of resisting electromagnetic interference is strong.
Main technical data
type |
Un (V) |
HZ |
1 m 1 |
1nc
l |
lnA |
lmA |
lmA |
The maximum of break-time(s) |
l |
2l |
5l |
0.25A |
500A |
G5SM1
2P |
240 |
50,
60 |
500A (l n = 50A 10ln)
(ln > 50A |
6000A |
6,10,
16,
25,
32,
40,
50,
63,
80 |
30 |
15 |
0.2 |
0.1 |
- |
0.04 |
0.04 |
50 |
25 |
0.2 |
0.1 |
- |
0.04 |
0.04 |
75 |
40 |
0.2 |
0.1 |
- |
0.04 |
0.04 |
100 |
50 |
0.2 |
0.1 |
0.04 |
- |
0.04 |
300 |
150 |
0.2 |
0.1 |
0.04 |
0.04 |
0.04 |
500 |
250 |
0.2 |
0.1 |
0.04 |
0.04 |
0.04 |
G5SM1
4P |
415 |
500A (l n = 50A
10ln)
(ln > 50A ) |
6000A |
6,10,
16,
25,
32,
40,
50,
63,
80 |
30 |
15 |
0.2 |
0.1 |
- |
0.04 |
0.04 |
50 |
25 |
0.2 |
0.1 |
- |
0.04 |
0.04 |
75 |
40 |
0.2 |
0.1 |
- |
0.04 |
0.04 |
100 |
50 |
0.2 |
0.1 |
0.04 |
- |
0.04 |
300 |
150 |
0.2 |
0.1 |
0.04 |
0.04 |
0.04 |
500 |
250 |
0.2 |
0.1 |
0.04 |
0.04 |
0.04 |
|